The event log is stored in non-volatile battery backed up RAM. Seventy-eight "snapshots" are recorded at the slow
cycle update rate, 58 before a fault occurs and 20 after. If the "Store in event log" is "On", several historical logs can
be stored. The maximum number is limited by the event log size (65kBytes).
Parameter
Store in event log
Historic log variable 1
Historic log variable 2
Historic log variable 3
Historic log variable 4
Historic log variable 5
Historic log variable 6
Historic log variable 7
Historic log upload
A1A19000405A: Version 1.3
Table 3-53: Historic Log Menu (6250)
ID
Default
6255
On
When selected, the Historical log is stored in the event log
Select the 1st variable for the historic log. See Table 3-54 for
6260
Spd Ref
pick list variables.
Select the 2nd variable for the historic log. See Table 3-54 for
6270
Trq I Cmd
pick list variables.
Select the 3rd variable for the historic log. See Table 3-54 for
6280
Mtr Flux
pick list variables.
Select the 4th variable for the historic log. See Table 3-54 for
6290
Pwr Out
pick list variables.
I Total
Select the 5th variable for the historic log. See Table 3-54 for
6300
Out
pick list variables.
Mag I
Select the 6th variable for the historic log. See Table 3-54 for
6310
Fdbk
pick list variables.
Select the 7th variable for the historic log. See Table 3-54 for
6320
Mtr Flux
pick list variables.
6330
Upload Historic log to serial port.
s s s s
The Keypad and Display Interface
Description
3
3-57

Advertisement

Table of Contents
loading

Table of Contents