Siemens PERFECT HARMONY GENIII/E Series User Manual page 23

Air cooled
Table of Contents

Advertisement

Perfect Harmony GENIII/e User's Manual
Output
Line-to-Line
Cells Per
Voltages(VAC)
Phase
3
3,300
4
4,160
6
6,600
Output
Line-to-Line
Cells per
Voltages (VAC)
Phase
2
2,300
3
3,300
4
4,160
5
6,000
6
6,600
The individual output cells are located in the Cell Section. All cells are electrically and mechanically identical, so that
they may be interchanged. Each cell contains its own control boards, which communicate with the system through a
fiber optic link. This link is the only connection between the cells and the master control located in the Control
Section, thus each cell is isolated from the main control. Refer to Figure 2-7 for GENIII type cell. Refer to Figure 2-8
and Figure 2-9 for GENIII/e type cells.
A1A19000405A: Version 1.3
Table 2-2: GENIII Cell Specification Details
Cells in Drive
hp Range
(Without
Spares)
9
up to 1500
12
up to 2000
18
up to 3000
Table 2-3: GENIII/e Cell Specification Details
Cells in Drive
Hp Range
(without spares)
6
up to 3000
9
up to 4000
12
up to 6000
15
up to 8000
18
up to 0000
Figure 2-7: Typical GEN III Cell
s s s s
Hardware Components
Available Cell Sizes
70A, 100A, 140A,200A, 260A
70A, 100A, 140A,200A, 260A
70A, 100A, 140A,200A, 260A
Available Cell Sizes
315A, 375A, 500A, 660A
315A, 375A, 500A, 660A
315A, 375A, 500A, 660A
315A, 375A, 500A, 660A
315A, 375A, 500A, 660A
2
2-9