Table 3-5: Summary of Operation Mode Displays: Line 2 of Mode Display
Code
Meaning
NOMV
No medium voltage
INH
CR3 inhibit
OFF
Idle state
MAGN
Magnetizing motor state
SPIN
Spinning load state
UXFR
Up transfer state
DXFR
Down transfer state
KYPD
Keypad speed demand
TEST
Speed/Torque test
LOS
Loss of Signal
AUTO
Automatic mode
NET1
Network 1
NET2
Network 2
DECL
Decelerating (no braking)
BRAK
Dynamic Braking
COAS
Coasting to stop
TUNE
Auto-Tuning
HAND
Hand mode
A1A19000405A: Version 1.3
Description
No input line voltage detected.
The CR3 or "Drive inhibit" input is asserted.
The drive is ready to run but is in an idle state.
The drive is magnetizing the motor.
The drive is trying to detect the speed of the motor to synchronize
the drive frequency.
The drive is in the "Up Transfer State" preparing to transfer the
motor to the input line.
The drive is in the "Down Transfer State" preparing to transfer the
motor from the input line to the drive.
The drive speed demand source is the keypad.
The drive is in a Speed or Torque test mode.
The drive 4-20mA analog input signal has dropped below a
predefined setting. See Tables 3-34, 3-35, 3-37, and 3-38.
The SOP flag AutoDisplayMode_O is set true usually to indicate
drive is receiving its speed demand from a source other than the
keypad or network. Typically used with a analog input speed
source.
Indicates drive is being controlled from Network 1.
Indicates drive is being controlled from Network 2.
The drive is decelerating normally.
Indicates that dynamic braking is enabled.
The drive is not controlling the motor and it is coasting to a stop
due only to friction.
The drive is in a "Auto-Tuning" mode used to determine motor
characteristics.
Appears if the drive is running under normal conditions.