The Keypad and Display Interface
Set
SOPConfigFileX_O
(X = 1 to 8)
3
Note: You do not need to add the file extension. The file extension is always 'sfg'. Press the 'enter' key
to save the parameter(s) as they exist in memory to a new configuration file name. This file will be
stored to the flash disk in the 'SubCfgs' subdirectory. This function does NOT make this configuration
file the active configuration file. It uses the current data in memory to create a new slave configuration
file. Any parameter that is saved to a slave configuration file is easily identifiable by the small 's'
adjacent to the parameter ID number if it has not changed from the default setting, or a '$' if it has been
changed from its default setting, i.e. (s9586) or ($9586).
3-70
This function allows you to map the name of the flag in the SOP file, SOPConfigFileX_O,
where X = 1 to 8, to a name of a slave configuration file. Then, when the SOP program is
running and this flag is set to 'true', the configuration file will be switched into memory.
This is a method of switching among multiple motors using one drive. The file names are
selected from a pick list. New files can be created using the method described previously.
s s s s
Perfect Harmony GENIII/e User's Manual
A1A19000405A: Version 1.3