Siemens PERFECT HARMONY GENIII/E Series User Manual page 62

Air cooled
Table of Contents

Advertisement

The Keypad and Display Interface
Parameter
0 Percent Break
Point
10 Percent Break
3
Point
17 Percent Break
Point
25 Percent Break
Point
50 Percent Break
Point
100 Percent Break
Point
Parameter
Auto-tune stage 1
Auto-tune stage 2
Auto-Tuning provides motor information that optimizes the Output Processing Control. Both stages of Auto-Tuning
are optional. The user can enter the motor information if available (see Table 3-11). The process is performed in two
stages.
3-26
Table 3-9: Speed Derate Curve Menu (1151)
ID
Units
Default
1152
%
0.0
1153
%
31.6
1154
%
41.2
1155
%
50.0
1156
%
70.7
1157
%
100.0
Table 3-10: Auto-Tune Menu (1250)
ID
Type
1260
Function
1270
Function
s s s s
Perfect Harmony GENIII/e User's Manual
Min
Max
Sets the maximum motor load at 0%
0.0
200.0
speed.
Sets the maximum motor load at 10%
0.0
200.0
speed.
Sets the maximum motor load at 17%
0.0
200.0
speed.
Sets the maximum motor load at 25%
0.0
200.0
speed.
Sets the maximum motor load at 50%
0.0
200.0
speed.
Sets the maximum motor load at 100%
0.0
200.0
speed.
Description
This function determines the stator resistance and leakage
inductance of the motor. The motor does not rotate during
this stage. If this function is not used the menu-entered values
are used.
This function determines the no-load current & rotor inertia
of the motor. The motor rotates during this stage. If this
function is not used the menu entered values are used.