Omron SYSMAC CS1W-CLK11 Operation Manual page 98

Table of Contents

Advertisement

Setting Data Links
Precautions
82
C200HX/HG/HE, CS/CJ-series, CVM1, CV-series, and CQM1H-series PCs
have different-sized memory areas. When data links are manually set, pro-
vided the PCs are set so as not to receive data in the areas indicated in the
following diagram, the data link setting area is not limited by the small area
size of the PC.
Example:
C200HX/HG/HE and
CQM1H-series PCs
235
If the LR Area in the C200HX/HG/HE or CQM1H Series is manually set for a
data link with a CVM1, CV-series or CS/CJ-series PC, the LR words will be
linked to CIO 1000 to CIO 1063 in the CVM1, CV-series or CS/CJ-series PC.
CIO 1064 to CIO 1199 cannot be linked with C200HX/HG/HE or CQM1H-
series PCs in this way.
C200HX/HG/HE and
CQM1H-series PCs
LR00
to
LR63
CVM1 and
CV-series PCs
0
100
to
335
336
CVM1, CV-series or
CS/CJ-series PCs
1000
to
1063
1064
to
Cannot be directly linked
with C200HX/HG/HE or
CQM1H words.
1199
Section 5-2
CS/CJ-series PCs
200
435
436

Advertisement

Table of Contents
loading

Table of Contents