C200HX/HG/HE Controller Link Units
4-3-2

Node Addresses

Note
4-3-3

Baud Rates and Operating Levels

Note
Baud Rate (Pins 1 and 2)
Set the node addresses of each Unit on the Network using the rotary switches
on the front of the Unit. The node address is used to identify each node in the
Network can be set to any number between 01 and 32.
Item
Setting method
Setting range
Node
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
1. Always turn OFF the PC's power before setting the node address.
2. Do not set the same node address twice within the same Network. An error
will occur if the same address is set for two different nodes. The ERC indi-
cator on the front of the Unit will light and either communications will stop,
or the INS indicator will not light and you will be unable to participate in the
Network.
3. The send sequence for the data link areas is determined according to the
sequence of node addresses for automatically set data links.
4. Assign node addresses consecutively beginning from 01 whenever possi-
ble to minimize Network construction time.
Set the following pins for the baud rate and operating level settings (DIP
switch).
SW1
ON
Note: The factory default settings are shown above.
1. Always turn OFF the PC's power before setting the baud rate or operating
level.
2. Keep pin 3 set to OFF. If it is turned ON, internal data may be erased.
Set the same baud rate for all the nodes on the Network using DIP switch pins
1 and 2 on the front of the Unit. The baud rate is set as shown below.
The maximum transmission distance will also change according to the setting.
Pins
Pin 1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
NODE NO.
1
X10
X10
0
1
1's digit
10's digit
Specifications
2-digit decimal
01 to 32 (default is 01)
All nodes in the Network
Pin 4:
Operating level
Pin 3:
Not used (must be OFF)
Pins 1, 2: Baud rate
Baud rate
Pin 2
2 Mbps
1 Mbps
500 Kbps
Do not set.
Section 4-3
0
Maximum transmission
distance
500 m
800 m
1 km