Omron SYSMAC CS1W-CLK11 Operation Manual page 129

Table of Contents

Advertisement

Introduction
C200HX/HG/HE PCs
SEND
@SEND(90)
S: Source node beginning send word
D: Destination node beginning receive word
S
C: Source node first control data word
D
C
15 14
C
0: Destination network address not specified (local network)
1: Destination network address specified.
15 14 13 12 11
C +1 1
Always "1" for Controller Link Networks
15
C + 2
Destination unit address
00 (Hex):
01 (Hex):
10 to 1F (Hex): Unit nos. 0 to 15
FE (Hex):
15
C + 3
Destination network address
00 (Hex): Local network
01 to 7F (Hex): 1 to 127
This setting is enabled only when Destination network address specified" is set in word C.
When specifying a destination network address, set all the nodes in the routing tables. For
details on routing tables, refer to
Note
SEND transmits "n" words beginning with S (the beginning source word for
data transmission at the source node) to the "n" words beginning with D (the
beginning destination word for data reception at destination node N).
0
"n" number of send words
0000 to 03DE (Hex): 0 to 990 words
8 7
0
Number of retries
0 to F (Hex): 0 to 15 retries
Direct/Indirect
Direct/Indirect
0: Direct; 1: Indirect
0: Response required
1: Response not required
0: Operating level 1
1: Operating level 0
8 7
0
PC's CPU Unit
Computer (user program)
Unit connected to network
0
0
0
Section 7 Network Interconnections.
1. When communicating in the same network with a CVM1 or CV-series PC
manufactured prior to April 1996, the local network address cannot be set
to "00." Set a number other than "00" as the local network address in the
routing tables, and then specify that number.
2. With the message service, there is no guarantee that a message to a des-
tination node will reach its destination. It is always possible that the mes-
sage may be lost in transit due to noise or some other condition. When
using the message service, it is advisable to prevent this situation from oc-
curring by performing resend processing at the node where instructions
are issued. With the SEND, RECV, and CMND instructions, resend pro-
Source node
15
0
S
"n" number
of send
words
n
Response monitor time
00 (Hex):
2 s (for 2 Mbps)
4 s (for 1 Mbps)
8 s (for 500 Kbps)
01 to FE (Hex):
0.1 to 25.4 s (unit: 0.1 s)
FF (Hex):
No response monitoring
Destination node address (N)
00 to 20 (Hex): 0 to 32
The same data can be broadcast to all nodes
on the network by setting the destination node
address to FF (Hex).
The range of node addresses will vary for networks
other than Controller Link Networks.
Section 6-1
Destination node N
15
0
D
n
113