Briggs & Stratton SIMPLIPHI Installation Manual page 39

6kw hybrid inverter
Table of Contents

Advertisement

Bulk Charging
07
Voltage (C.V.
Voltage)
Floating
Charging
Voltage
08
Low DC cut off
battery voltage
setting when
09
grid is
unavailable
Battery re-
discharging
10
voltage when
grid is
unavailable
Low DC cut off
battery voltage
11
when grid is
available
Battery re-
discharging
12
voltage when
grid is available
13
Operation Mode
© SIMPLIPHI POWER
Default setting: 56.0V
Default setting: 54.0V
Default setting:42.0
Default setting:48.0
Default setting:48.0
Default setting:54.0
Grid-tie with backup
Off-Grid
Grid-Tie
Grid-tie with Backup Mode
Grid-tie with backup I
Battery-Load-Grid:
PV will charge the battery first. Then it will
provide power to the load. If there is any
remaining power left, it will be fed into the
grid.
| 39 |
Setting range is from 48.0V to 60.0V. Each
click will increment by 0.1V
Setting range is from 48.0V to 60.0V. Each
click will increment by 0.1V
Setting range is from 40V to 60V. Each click
will increment by 0.1V.
This value will be
dictated by the CAN connected battery
voltage settings (Setting 3) within the BMS for
LBCO.
Setting range is form 40V to 60V. Each click
will increment by 0.1V.
Setting range is from 42V to 60V voltage.
Each click will increment by 0.1V
Setting range is from 42V to 60V voltage.
Each click will increment by 0.1V
PV power can feed-in back to the grid, provide
power to the load and charge the battery
It only provides PV power to the load and
charges the battery. It is not able to feed back
to the grid. Grid power is not available.
No batteries are present, PV power only
powers loads and feeds back to the grid
REV2022007071630