Eev Control - Friedrich VRP Series Service & Parts Manual

Hide thumbs Also See for VRP Series:
Table of Contents

Advertisement

Component Identification

EEV Control

The Electronic Expansion Valve is used to maintain
superheat during both cooling and heat pump operation.
Superheat (cooling) = Compressor Suction (T3) – IDC
Cool Inlet (T1)
Superheat (heat pump) = Compressor Suction (T3) –
ODC Heat Inlet (T7)
The EEV will open if the super heat is too high and will
meter if the super heat is too low.
38
OPERATION
COMPONENT IDENTIFICATION-EEV CONTROL
FIGURE 314 (
)