COMPONENTS TESTING

Check Basepan Heater

CONDENSER
BASEPAN
HEATER
L1
L2
T-STAT
1. Remove power from unit.
2. Check fuses for continuity. Replace fuses as required.
3. Check Basepan inline TSTAT.
Open On Rise (Normally Closed)Open Temperature: 50°F ± 5°F Close Temperature: 32°F ± 11°F
Strip back heatshrink and check that switch is closed if below 32 degrees and open if above 50 degrees
4. Reinstall heat shrink
5. OHM out basepan heater element for resistance. If element is open, replace heater.