E5AN-H/E5EN-H
Electrical Life Expectancy Curve for
Relays (Reference Values)
500
300
E5AN-H/E5EN-H
100
250 VAC, 30 VDC
(resistive load)
cosφ = 1
50
30
10
5
3
1
0
1
2
3
52
4
5
6
Switching current (A)
SSR Outputs (OUT1/OUT2) Ratings
• Rated load voltage: 75 to 250 VAC
• Rated load current: 1 A (resistive load)
Note: 1. The load current must be within the derating curve.
2. There is no zero-cross function.
Derating Curve for SSR Outputs (Reference Values)
1.5
1.25
1
0.75
0.5
Condition A
0.25
0
−10
0
10
20
30
Ambient temperature (°C)
Condition A: SSR outputs 100% ON
Condition B: SSR outputs 50% ON with 2-s control cycle
Condition B
40
45
50 55