Omron E5 N-H Series Manual page 24

Digital temperature controllers/digital controllers
Hide thumbs Also See for E5 N-H Series:

Advertisement

E5AN/E5EN
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
Set
Alarm type
value
Alarm function
0
Output OFF
OFF
Upper- and
1
✽1
lower-limit
2
Upper limit
3
Lower limit
Upper- and
4
✽1
lower-limit range
Upper- and
lower-limit with
5
✽1
standby
✽5
sequence
Upper-limit with
6
standby
sequence
Lower-limit with
7
standby
sequence
Absolute-value
8
upper-limit
Absolute-value
9
lower-limit
Absolute-value
upper-limit with
10
standby
sequence
Absolute-value
lower-limit with
11
standby
sequence
LBA (for alarm 1
12
---
only)
PV change rate
13
---
alarm
24
Alarm output operation
When X is
When X is
positive
negative
L
H
ON
✽2
OFF
SP
X
X
ON
ON
OFF
OFF
SP
SP
X
ON
ON
OFF
OFF
SP
SP
L
H
ON
✽3
OFF
SP
L
H
ON
✽4
OFF
SP
X
X
ON
ON
OFF
OFF
SP
SP
X
ON
ON
OFF
OFF
SP
SP
X
X
ON
ON
OFF
OFF
0
X
X
ON
ON
OFF
OFF
0
X
X
ON
ON
OFF
OFF
0
X
X
ON
ON
OFF
OFF
0
✽1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
"L" and "H."
✽2. Set value: 1, Upper- and lower-limit alarm
Case 1
L
H
SP
H < 0, L > 0
H < L
✽3. Set value: 4, Upper- and lower-limit range
X
Case 1
L
H SP
H < 0, L > 0
H < L
✽4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
• Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
X
• Case 3: Always OFF
✽5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
0
overlaps.
0
0
0
Case 2
Case 3 (Always ON)
H
SP
L
SP
L H
H > 0, L < 0
H
L
SP
H > L
SP
H
L
Case 3 (Always OFF)
Case 2
H SP
L
SP
L
H
H > 0, L < 0
H > L
H
L
SP
L
SP
H
H < 0, L < 0
H < 0, L > 0
H ≥ L
H > 0, L < 0
H ≤ L
H < 0, L < 0
H < 0, L > 0
H ≥ L
H > 0, L < 0
H ≤ L

Advertisement

loading

This manual is also suitable for: