External Connections
• A voltage output (control output, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
Controllers
Control output 1
Relay output
250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
12 VDC, 21 mA
Linear voltage output
0 to 10 VAC
Load 1 kΩ max.
mA
Current output
0 to 20 mA DC
DO NOT
4 to 20 mA DC
USE
Load 600 Ω max.
Option Units
E53-CNBN2
Event Inputs
11
12
EV1
13
EV2
DO NOT
14
Control output 2
USE
12 VDC 21 mA
DO NOT
15
USE
E53-CNQHHN2
Control Output 2
and CT2
11
Control output 2
Control output 2
12 VDC 21 mA
12 VDC 21 mA
12
13
CT2
14
CT1
Transfer output
15
E53-CN03N2
E53-CNQ03N2
Communications
Communications (RS-485)
(RS-485)
and Control Output 2
B (+)
11
RS-485
12
A (−)
DO NOT
13
USE
DO NOT
14
USE
Control output 2
12 VDC 21 mA
DO NOT
15
USE
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
1
Control output 1
2
DO NOT
DO NOT
A
3
USE
USE
B
4
V
B
5
E53-CNQBN2
Event Inputs and
Control Output 2
11
12
EV1
13
EV2
EV2
14
CT1
15
E53-CNQFN2
Control Output 2 and
Transfer Output
RS-232C
11
12
DO NOT
13
USE
DO NOT
14
USE
4 to 20 mA DC
(Load 600 Ω
DO NOT
15
USE
max.)
B (+)
11
RS-485
RS-485
12
A (−)
DO NOT
DO NOT
13
USE
USE
14
CT1
15
Auxiliary outputs
(relay outputs)
11
6
Auxiliary output 2
12
7
Auxiliary output 1
8
13
?
14
9
Input power supply
15
10
E53-CNHBN2
E53-CNBFN2
Event Inputs
Event Inputs and
and CT
Transfer Output
11
12
EV1
EV1
13
EV2
14
Transfer output
15
E53-CN01N2
E53-CNH01N2
Communications
Communications
(RS-232)
(RS-232) and CT
RS-232C
SD
SD
11
RD
RD
12
SG
SG
13
14
CT1
15
E53-CNH03N2
E53-CNHH03N2
Communications
Communications
(RS-485) and CT
(RS-485) and CT2
B (+)
B (+)
11
RS-485
12
A (−)
A (−)
13
CT2
14
CT1
15
E5CN-H
Auxiliary outputs (relay outputs)
250 VAC, 3 A
(resistive load)
A heater burnout alarm, SSR
failure, heater overcurrent alarm,
or input alarm is sent to the
output to which the alarm 1
function is assigned.
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
11
12
13
14
4 to 20 mA DC
(Load 600 Ω max.)
15
E53-CNQ01N2
Communications (RS-232)
and Control Output 2
RS-232C
SD
11
11
RD
12
12
SG
13
13
14
14
Control output 2
12 VDC 21 mA
15
15
E53-CNQHN2
Control Output 2
and CT
11
11
Control output 2
12 VDC 21 mA
12
12
DO NOT
13
13
USE
14
14
CT1
15
15
39