Omron NX-PA Series User Manual page 56

Machine automation controller
Table of Contents

Advertisement

1 Introduction to NX-series Controllers
Built-in
Ether-
OPC UA Server
Net/IP port
1 - 10
Item
Support profile/Model
Default Endpoint/Port
Maximum number of sessions (Client) 5
Maximum number of Monitored Items
per server
Sampling rate of Monitored Items (ms)
Maximum number of Subscriptions
per server
Maximum number of variables that
can be published
Maximum number of value attributes
that can be published
Maximum number of structure defini-
tions that can be published
*8
Restrictions on variables unable to be
published
Security Policy/Mode
Authentication
Application
Maximum number of
storable certifica-
Authentication
tions
User Authenti-
Authentication
cation
17
Micro Embedded Device Server
Profile
PLCopen Information Model
opc.tcp://192.168.250.1:4840/
2,000
*9
0
, 50, 100, 250, 500, 1,000, 2,000,
5,000, 10,000
100
10,000
10,000
*10
100
• Variables whose size is over 1,024
bytes
• Two-dimensional or higher structure
arrays
• Structures that include two-dimen-
sional and higher arrays
• Structures with four or higher levels of
nesting
• Unions
• Arrays whose index number suffix
does no start from 0
• Arrays with 1,024 or more elements
• Structures with 100 or more members
Select one of the following.
• None
• Sign - Basic128Rsa15
• Sign - Basic256
• Sign - Basic256Sha256
• SignAndEncrypt - Basic128Rsa15
• SignAndEncrypt - Basic256
• SignAndEncrypt - Basic256Sha256
X.509
Trusted certification: 32
Issuer certification: 32
Rejected certification: 32
You can set the following items.
User name/Password
Anonymous
NX-series CPU Unit Hardware User's Manual (W535)
NX701-

16


Advertisement

Table of Contents
loading