4 Installation and Wiring
Installation Height
With a height of 100 mm, the CPU Unit is the highest component in an NX-series CPU Rack. When a
cable is connected (such as a Unit communications cable), however, even greater height is required.
Allow sufficient depth in the control panel containing the Controller.
The following figure shows the dimensions from the cables connected to the CPU Rack to the back of
the Unit. The unit of dimension is millimeter.
The height from the mounting surface of the DIN Track varies depending on the DIN Track to be used.
Refer to Installation Dimensions on page 4-29 for the height of individual DIN Track type.
*1. This is the dimension from the back of the Unit to the communications cables.
130 mm: When an MPS588-C Connector is used.
155 mm: When an XS6G-T421-1 Connector is used.
*2. This dimension depends on the specifications of the commercially available USB cable. Check the specifica-
tions of the USB cable that is used.
4 - 30
100
130 to 155 *1
*2