Periodic Inspection Items
Inspec-
No.
tion item
1
External
power
supply
2
I/O power
supply
3
Ambient
environ-
ment
4
Installa-
tion and
wiring
NX-series CPU Unit Hardware User's Manual (W535)
Inspection details
Check for voltage fluctua-
tions at the power supply ter-
minals.
Check for voltage fluctua-
tions at the I/O terminals.
Check the ambient tempera-
ture.
(Inside the control panel if the
Controller is in a control
panel.)
Check the ambient humidity.
(Inside the control panel if the
Controller is in a control
panel.)
Check that the Controller is
not in direct sunlight.
Check for accumulation of
dirt, dust, salt, metal powder,
etc.
Check for water, oil, or chem-
ical sprays hitting the Con-
troller.
Check for corrosive or flam-
mable gases in the area of
the Controller.
Check the level of vibration
or shock.
Check for noise sources near
the Controller.
Check that each Unit is con-
nected and locked to the next
Unit securely.
Check that cable connectors
are fully inserted and locked.
Check for loose screws in
external wiring.
Check crimp connectors in
external wiring.
Check for damaged external
wiring cables.
6 Inspection and Maintenance
Criteria
The voltage must be
Use a voltage tester to check the
within the allowable
power supply at the terminals. Take
voltage fluctuation
necessary steps to bring voltage of
range.
the supplied power to within the
allowable voltage fluctuation range.
Voltages must be within
Use a voltage tester to check the I/O
specifications for each
power supply at the terminals. Take
Unit.
necessary steps to bring voltage
fluctuations within limits.
0 to 55°C
Use a thermometer to check the
temperature and ensure that the
ambient temperature remains within
the allowed range of 0 to 55°C.
Relative humidity must
Use a hygrometer to check the
be 10% to 95% with no
humidity and ensure that the ambi-
condensation.
ent operating humidity remains
between 10% and 95%.
Make sure that condensation does
not occur due to rapid changes in
temperature.
Not in direct sunlight
Protect the Controller if necessary.
No accumulation
Clean and protect the Controller if
necessary.
No spray
Clean and protect the Controller if
necessary.
No corrosive or flam-
Check by smell or use a gas sensor.
mable gases
Vibration resistance
Install cushioning or shock absorb-
and shock resistance
ing equipment if necessary.
must be within specifi-
cations.
No significant noise
Either separate the Controller and
sources
noise source or protect the Control-
ler.
No looseness
Press the connectors together com-
pletely and lock them with the slid-
ers.
No looseness
Correct any improperly installed
connectors.
No looseness
Tighten loose screws with a Phil-
lips-head screwdriver.
Adequate spacing
Check visually and adjust if neces-
between connectors
sary.
No visible damage
Check visually and replace cables if
necessary.
Correction