System Operation and Functions
Under exit-only muting mode
1. Muting sequence error occurred
2. The F3SG-RA is blocked and the output is OFF.
3. Under the state of 1 and 2, a special sequence is entered to the reset input three (3) times. The
signal must be entered within a range from 0.1 s to the override input time limit T1 (1 s) (can be
changed). (See the timing chart below.)
Override end conditions under normal operation
When any of the following conditions is satisfied, the override state is released.
Override state can be also released when the F3SG-RA enters the Lockout state.
Under standard muting mode
1. A period of 600 s (configurable) passes in the OVERRIDE state
2. All muting inputs are turned OFF.
3. The following signal to cancel the OVERRIDE state is entered:
• When the external device monitoring function is enabled, the RESET line is turned ON. (PNP:
Connected to Vs-3 V~Vs; NPN: Connected to 0 V~3 V)
• When the external device monitoring function is disabled, the RESET line is turned OFF.
Under position detection muting mode
1. A period of 600 s (configurable) passes in the OVERRIDE state
2. When muting input A is OFF and muting input B is ON
3. The following signal to cancel the OVERRIDE state is entered:
• When the external device monitoring function is enabled, the RESET line is turned ON. (PNP:
Connected to Vs-3 V~Vs; NPN: Connected to 0 V~3 V)
• When the external device monitoring function is disabled, the RESET line is turned OFF.
Under exit-only muting mode
1. A period of 600 s (configurable) passes in the OVERRIDE state
2. When F3SG-RA is unblocked
3. The following signal to cancel the OVERRIDE state is entered:
• When the external device monitoring function is enabled, the RESET line is turned ON. (PNP:
Connected to Vs-3 V~Vs; NPN: Connected to 0 V~3 V)
• When the external device monitoring function is disabled, the RESET line is turned OFF.