System Operation and Functions
 Timing chart
Muting input A
Muting input B
Muting state
Beam state
OSSD
 Default settings
Variable
T
1min
T
1max
T
2
T
3
 Wiring diagram
Power supply
S1, S2:
F3SG-R
50
User's Manual
ON
OFF
T1min to T1max
ON
OFF
80 ms max.
Enabled
Disabled
Unblocked
Blocked
ON
OFF
Variable name
Muting input time limit value
(minimum)
Muting input time limit value
(maximum)
Muting time limit
Maximum allowable muting
signal interruption
PNP output
F39-JG A-D
S1
S2
+24 VDC
0 VDC
Muting sensor
T3 max.
T3 max.
T2 max.
Value
0.1 s
Minimum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is smaller
than this value, a muting sequence error occurs.
4 s
Maximum time difference between muting inputs A and B.
If the time difference between muting inputs A and B is larger
than this value, a muting sequence error occurs.
60 s
The duration time of the Muting function. The Muting state is
cancelled if it continues for longer than this time limit.
0.1 s
Maximum duration of a signal interruption allowed in muting
inputs A and B.
+24 VDC
Power supply
0 VDC
S1, S2:
Description
NPN output
F39-JG A-D
S1
S2
Muting sensor