Flueing Arrangements - Horizontal; Terminations: All Systems; Flueing Arrangements - Vertical Terminations; Straight Vertical - Regency FireGenieFG39-LPG2 Owners & Installation Manual

Freestanding gas stove
Table of Contents

Advertisement

installation
FLUEING ARRANGEMENTS
Horizontal Terminations for All Flueing Systems
The shaded areas in the diagram below show all allowable combina-
tions of vertical runs with horizontal terminations. Maximum one
90
elbow (two 45
elbows equal one 90
O
o
LPG and NG:
The flueing arrangements diagrammed below, have a minimum of 75%
(flue loss) efficiency with Fan Off, as required for manufactured homes.
(Actual efficiency may be as high as 85%)
1.5m
Min.
7.3m
0.3m
6.7m
6.1m
5.5m
4.9m
4.3m
3m
2.4m
1.8m
1.2m
0.9m
0.6m
Horizontal Run (Metres)
10
elbow).
o
3.7m Max.
1
1
Vertical Terminations Using
Dura-Flue Flueing System
The shaded area in the diagram below shows all allowable combi-
nations of straight vertical and offset to vertical runs with vertical
terminations. Maximum two 45
If the flue is ENCLOSED in a chase 229mm x 229mm maintain a 32mm
clearance to combustibles.
1.8m Max.
9.1m
7.9m
7.9m
7.3m
6.7m
6.1m
5.5m
4.9m
4.3m
3.7m
3m
2.4m
1
45
1.8m
1.2m
0.6m
Horizontal Distance (Metres)
elbows.
o
1
o
FG39-2 Freestanding Gas Stove