6. REFRIGERATION CHARGE & PIPE-WORK
Both indoor and outdoor units come delivered under positive pressure
The outdoor unit is charged with sufficient R410a refrigerant for an interconnecting pipe run
WARNING
of 15m actual length
The indoor unit is pressurised with 400kPa to 700kPa dry nitrogen
Pipe end blanking plates must not be removed until the installer is sure the plates are not
under positive pressure.
A suction accumulator has been fitted in the outdoor units
Read all instructions and notes below before starting installation
Use new, clean and sealed refrigeration grade pipe suitable for R410a
Keep pipe ends sealed, both before and during installation, to avoid entry of moisture
CAUTION
Suspend pipes with hangers or straps and seal openings around pipe penetrations with
flexible material.
Consider pipe expansion and leave space between pipes and adjacent structures
Use brazing shields where required
When brazing in the vicinity of valves likely to be affected by heat, they shall be lagged with
a wet cloth
All brazing operations must be completed with a small steady stream of nitrogen passing
through the pipe-work to limit scale build up and moisture contamination
Never use the unit compressor as a vacuum pump
6.1

PIPING DESIGN

Pipe-work shall be installed in a manner which prevents drainage of liquid into the compressor and ensures
adequate oil return
Pipe insulation should be nitrile rubber, 13mm thick for pipes up to and including 20mm diameter and 19mm
thick for pipes above 20mm in diameter
It is generally necessary to insulate the suction pipe only. However, it is recommended the liquid line pipe also
be insulated where it is exposed to direct sunlight or if located in hot surroundings such as ceiling void, or
buried underground
Pipes should be run as directly as possible between indoor and outdoor units
If the indoor coil is located above the condensing unit the suction line shall have a loop at the evaporator outlet
to prevent refrigerant drainage into the compressor during off cycle
If the evaporator is located below the condensing unit, then the suction riser shall be U-Trapped at 3m above
ground level
Avoid burying pipes below ground. If necessary, they shall be insulated and encased in a PVC pipe, sealed at
both ends where the pipe exits above ground. The buried distance shall not exceed 5 metres and a liquid line
solenoid valve, interlocked with the compressor, shall be located adjacent to the indoor unit
Care should be taken if running pipe-work within wall cavities as this may lead to transmission of refrigerant
noise into the occupied space. The use of mufflers or oil separator can help reduce potential pulsation in the
discharge line
Brivis
46