Refrigerant Piping Connection

When connecting refrigerant piping, do not let substances or gases other than the specified
refrigerant enter the unit. The presence of other gases or substances will lower the unit's capacity,
and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and
injury.

Note on Pipe Length

Note on Pipe Length
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal
efficiency is tested on units with a pipe length of 5 meters (16.5ft). A minimum pipe run of 3 metres is
efficiency is tested on units with a pipe length of 5 meters (16.5ft)( In North America, the standard pipe
required to minimise vibration & excessive noise.
length is 7.5m (25')). A minimum pipe run of 3 metres is required to minimise vibration & excessive noise.
In special tropical area, for the R290 refrigerant models, no refrigerant can be added and the maximum
In special tropical area, for the R290 refrigerant models, no refrigerant can be added and the maximum
length of refrigerant pipe should not exceed 10 meters (32.8ft).
length of refrigerant pipe should not exceed 10 meters(32.8ft).
Refer to the table below for specifications on the maximum length and drop height of piping.
Refer to the table below for specifications on the maximum length and drop height of piping.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model
Model
R410A,R32 Inverter
Split Air Conditioner
R22 Fixed-speed
Split Air Conditioner
R410A, R32 Fixed-speed
Split Air Conditioner
Connection Instructions – Refrigerant Piping
Connection Instructions – Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
and outdoor units.
2. Using a pipe cutter, cut the pipe a little longer
than the measured distance.
3. Make sure that the pipe is cut at a perfect 90°
angle.
Rinnai
REFRIGERANT PIPING CONNECTION
Capacity (BTU/h)
< 15,000
≥ 15,000 and < 24,000
≥ 24,000 and < 36,000
< 18,000
≥ 18,000 and < 21,000
≥ 21,000 and < 35,000
< 18,000
≥ 18,000 and < 36,000
23
Max. Length (m)
25 (82ft)
30 (98.5ft)
50 (164ft)
10 (33ft)
15 (49ft)
20 (66ft)
20 (66ft)
25 (82ft)
90°
Oblique Rough Warped
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
deform the pipe while cutting. This will
drastically reduce the heating efficiency
drastically reduce the heating efficiency
of the unit.
of the unit.
Max. Drop Height (m)
10 (33ft)
20 (66ft)
25 (82ft)
5 (16ft)
8(26ft)
10(33ft)
8(26ft)
10(33ft)
Page 29
Split AC IM