4: Installing The Panel Circuit Modules; 5: Connecting Icm-4Rk And Ice-4 Modules - Honeywell XLS140 Installation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation
Group of panel
modules in second
Group of panel
modules in third
cabinet row
3.12.4 Installing the Panel Circuit Modules
To install a panel circuit module such as the ICM-4RK or CRM-4RK into the chassis:
1.
Angle the module into the chassis so that the lower board edge slips into the chassis slots as
shown in Figure 3.7.
2.
Push the upper end of the module into the upper opening in the chassis.
3.
Secure the module to the chassis with the two module screws (provided with the module).
Tighten securely.
4.
Connect the Ribbon Cable to the module.
3.12.5 Connecting ICM-4RK and ICE-4 Modules
The total current available for any group of Notification Appliance Circuits (NACs), other than the
four NACs on the control panel, cannot exceed the following:
6.0 A when powered from the APS-6R
1.25 A when powered from a XLS140 DC power output terminal
Figure 3.19 shows the wire connectors on the bottom of the ICM-4RK and the ICE-4 modules.
46
J6 - Third Row
Expander Row Ribbon Cable (P/N 71088)
MODULE
MODULE
TYPE
TYPE
LAMPS
LAMPS
SWITCH
SWITCH
cabinet row
P1.1–P1.8
Expander Row Ribbon Cable (P/N 71088)
MODULE
MODULE
TYPE
TYPE
LAM PS
LAM PS
SWITCH
SWITCH
P5.1–P5.8
Figure 3.18 Expander Row Ribbon Cable Setup
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
J5 - Second Row
MODULE
MODULE
MODULE
MODULE
TYPE
TYPE
TYPE
TYPE
LAMPS
LAMPS
LAMPS
LAMPS
SWITCH
SWITCH
SWITCH
SWITCH
P2.1–P2.8
P3.1–P3.8
MODULE
MODULE
MODULE
MODULE
TYPE
TYPE
TYPE
TYPE
LAM PS
LAMPS
LAMPS
LAMPS
SWITCH
SWITCH
SWITCH
SWITCH
P6.1–P6.8
P7.1–P7.8
Installing Panel Circuit Modules
MODULE
MODULE
TYPE
TYPE
LAMPS
LAMPS
SWITCH
SWITCH
P4.1–P4.8
MODULE
MODULE
TYPE
TYPE
LAMPS
LAMPS
SWITCH
SWITCH
P8.1–P8.8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents