Setting CRT-2 Parameters

The CRT-2 communicates with the control panel through a protocol defined by thirteen groups of
parameters. To access a parameter group, press the corresponding function key (F1-F12) as shown
in Table 3.7 below. You can then program parameters in each group.
Enter the CRT-2 setup menu by pressing and holding the <Ctrl> key while pressing the <Scroll
Lock> key. Use arrow keys to move through the selections in each setup group; press the space bar
to view the options for each parameter. When finished programming all setup groups, press the
<Pause> key. To save all changes, press <Y>.
Table 3.7 shows the standard settings for using the CRT-2 with the XLS140; for one instance where
these settings may change slightly see Section 3.14.6 "Connecting Multiple Printers, CRTs, or
CRT/PRN Combination". The basic settings for using the CRT-2 with XLS140 are:
• Baud Rate 9600 • Data format 8 1 N • Protocol xon/off.
NOTE: This section covers installation only; for information on how the CRT-2 functions as part
of the fire alarm system, see the XLS140 Operations Manual.
Function Key
CRT-2 Parameters
F1: Quick
Emulation=CRT-2
("Read Status" key)
Comm Mode=Full Duplex
Enhanced=On
F2:Genrl
Emulation=CRT-2
("Alter Status" key)
Auto Font Load=On
Monitor Mode=Off
Host/Printer=EIA/Aux
F3: Displ
Page Length=24
("Prog" key)
Display Cursor=On
Columns=80
Scroll=Jump
F4: Kybd
Language=U.S.
("Spl Funct" key)
Keyclick=Off
Key Lock=Caps
F5: Keys
Enter Key=<CR>
("Prior" key)
Alt Key=Meta
Pound Key=U.S.
F6: Ports
EIA Baud Rate=9600
("Next" key)
Aux Baud Rate=9600
EIA Xmt=Xon-Xoff
Aux Xmt=Xon-Xoff
EIA Break=Off
Aux Break=Off
Table 3.7 Standard CRT-2 Settings for Use with XLS140 (Sheet 1 of 2)
54
DB-25 connector
on CRT-2 (female
socket shown)
PRINTER
PC/CRT
TX
RX
REF
TX
RX
Control
Panel
TB14
Figure 3.28 Connecting a CRT-2
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
Installing Remote Printers and/or CRT
Terminate one end of
shield at backbox
REF
TB15
EIA Baud Rate=9600
Aux Baud Rate=9600
Language=U.S.
Enhanced=On
Auto Page=Off
Bell Volume=09
Screen Length=26 Lines
Cursor=Blink Line
Width Change Clear=Off
Refresh Rate=60 Hz
Char Set Mode=ASCII
Key Repeat=Off
Keyboard Present=Yes
Return Key=<CR>
Disconnect=Pause
EIA Data Format=8/1/N
Aux Data Format=8/1/N
EIA Recv=Xon-Xoff(XPC)
Aux Recv=Xon-Xoff(XPC)
EIA Modem Control=Off
Aux Modem Control=Off
EIA Data Format=8/1/N
Aux Data Format=8/1/N
Host/Printer=EIA/Aux
Auto Wrap=Off
Auto Scroll=On
Warning Bell=On
Screen Video=Normal
Auto Adjust Cursor=On
Speed=Normal
Overscan Borders=Off
Key Mode=ASCII
Margin Bell=Off
Backspace=<BS>/<DEL>
Desk Acc=Disabled
EIA Parity Check=On
Aux Parity Check=On
EIA Xmt Pace=Baud
Aux Xmt Pace=Baud
EIA Disconnect=2 sec
Aux Disconnect=2 sec