Honeywell XLS140 Installation Manual page 80

Fire alarm control panel
Table of Contents

Advertisement

Electrical Specifications
Circuit
Circuit Type
Function
SLC
Connects to
(power limited)
intelligent and
addressable
modules.
or
EIA-485
Connects to
(power limited)
XLS-LCD-80,
ACS modules,
or TM-4
Transmitter
EIA-232
Connects to
(power limited)
Printers, CRT,
or PC.
IDC
XLS-MM-A/
Initiating Device
TC809A1059,
Circuit
XLS-MM-B/
TC809B1008,
XP5-M,
XP10-M,
XP6-MA
(power limited)
NAC
XLS-CM-N/
Notification
TC810N1013,
Appliance
XP6-C (power
Circuit
limited)
24 VDC Power
To TM-4
Runs
Transmitter,
(power-limited)
Annunciator and
XLS-CM-N/
TC810N1013
modules
CHG-120
External battery
charger
*
Notifier brand cable is recommended; see the product catalog available from Paige Electric.
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length
maximum to meet UL 1459.
80
Wire Requirements
Twisted-unshielded pair, 12 to 18 AWG
2
(3.31 to 0.82 mm
). 50 ohms maximum per
length of Style 6 & 7 loops. 50 ohms per
branch maximum for Style 4 loop.
Untwisted, unshielded wire, in conduit or
outside of conduit.
Note: Maximum total capacitance of all
SLC wiring (both between conductors and
from any conductor to ground) should not
exceed 0.5 mircofarads.
Twisted-shielded pair with a characteristic
impedance of 120 ohms. 18 AWG (0.82
2
mm
) minimum.
Twisted-shielded pair in conduit.
2
18 AWG (0.82 mm
) minimum.
2
12-18 AWG (3.31 to 0.82 mm
Maximum circuit resistance is 20 ohms.
2
12-18 AWG (3.31 to 0.82 mm
At alarm current level, no more than a 1.2
V drop at the end of the circuit, or sized to
provide the minimum rated operating
voltage of the appliances used.
2
12-18 AWG (3.31 to 0.82 mm
Size wire so that no more than 1.2 V drop
across wire run from supply source to end
of any branch.
2
12 AWG (3.31 mm
) in conduit
Table B.1 Wire Requirements
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
Distance
(feet/meters)
12,500 ft. (3,810 m)
9,500 ft. (2,895.6 m)
6,000 ft. (1,828.8 m)
3,700 ft. (1,127.76 m)
1,000 ft. (304.8 m)
6,000/1829
(max)
50/15.24
(without modem)
).
).
To meet 1.2 V drop,
or sized to provide
the minimum rated
operating voltage of
the appliances used.
).
To meet 1.2 volt drop
20/6.1 (max)
Wire Requirements
*
Typical Wire Type
2
12 AWG (3.31 mm
)
2
14 AWG (2.08 mm
)
2
16 AWG (1.31 mm
)
2
18 AWG (0.82 mm
)
12 to 18 AWG (3.31 to
2
0.82 mm
)
2
16 AWG (1.31 mm
)
2
16 AWG (1.31 mm
)
12 to 18 AWG (3.31 to
2
0.82 mm
)
12 to 18 AWG (3.31 to
2
0.82 mm
)
12 to 18 AWG (3.31 to
2
0.82 mm
)
2
12 AWG (3.31 mm
)