Panel Circuit Modules

Printer - PRN Series Printer The PRN is an optional printer that connects directly to the
control panel through an EIA-232 interface (TB14) and can be located up to 20 feet (6.1 m) from
the control panel. It creates a printed record (80 columns of data on standard 9" x 11" tractor-feed
paper) of all system events (alarm, trouble) and status changes within the system. The printout is
time-stamped with the current time-of-day and date.
Keltron Remote Printer The VS4095 is a two-color (red/black), 40-column, 24 VDC printer
that can print 50 messages in 90 seconds. This printer connects to the control panel through an
EIA-232 interface (TB14) and mounts in a separate cabinet next to the control panel. The VS4095
meets UL fire and security requirements for an ancillary device.
For more information, contact the manufacturer (Keltron Corp., Waltham, MA)
Display Terminal - CRT-2 This optional display terminal connects to the control panel through
an EIA-232 interface (TB15). The terminal can control and view events, points and history reports,
control the system (Acknowledge, Alarm Silence, and System Reset). The terminal displays 26
lines by 80 columns and can be located up to 50 feet (15.24 m) from the control panel within the
same room.
NOTE: The CRT cannot be connected at the same time as the network.
2.10 Panel Circuit Modules
Introduction
The control panel supports the following modules to control external circuits and relays:
Indicating Circuit Module (ICM-4RK) & Indicating Circuit Expander (ICE-4)
Control Relay Module (CRM-4RK) & Control Relay Expander (CRE-4)
Auxiliary Relay Module (ARM-4)
Voice Control Module (VCM-4RK), Dual Channel Module (DCM-4RK) & Voice Control
Expander (VCE-4)
Up to eight of these modules (in any combination) can be controlled by the panel. Below are brief
descriptions of the modules; for a description of VCM-4RK and DCM-4RK, see Section 2.11
"Voice Alarm System".
Indicating Circuit Module - ICM-4RK Provides four (4) NACs for Style Y (Class B) or Style
Z (Class A) operation. Circuits are field-programmable to respond to a single initiating zone, a
group of zones, or all initiating zones. Maximum signaling current is 3 A per circuit or 6 A per
module, limited by the power supply.
An Auxiliary Power Harness (P/N 71091) is provided. Note: ICM-4RK is not listed for use with
XLS140 in releasing applications.
Indicating Circuit Expander - ICE-4 An attaching circuit board that expands the ICM-4RK to
a total of eight Style Y (Class B) or Style Z (Class A) NAC's. Maximum signaling current is 3 A
per circuit or 6 A per module, limited by the power supply. An Auxiliary Power Harness (P/N
71091) is provided.
Control Relay Module - CRM-4RK Provides four (4) standard dry Form-C relay contacts.
Each relay is field-programmable to respond to a single initiating device circuit, a group of circuits,
or all initiating device circuits. Each relay features manual On/Off control switches and can be
disabled or enabled. Contacts rated for 5 A at 120 VAC or 28 VDC (resistive). Note: CRM-4RK is
not listed for use with XLS140 in releasing applications.
Control Relay Expander - CRE-4 An attaching circuit board that expands the capacity of the
Control Relay Module (CRM-4RK) to eight (8) Form-C alarm relays. May also be used to expand
the ICM-4RK to provide four (4) Form-C control relays. Contacts rated for 5 A at 120 VAC or 28
VDC (resistive).
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
System Overview
25