3.12.6 Field-Wiring the ICM-4RK and ICE-4 (NFPA Style Y or Z)
Guidelines for field-wiring:
Notification Appliance Circuits (NACs) are supervised, power-limited, and can connect to a
power-limited cable.
Use only the compatible, UL-listed notification appliances listed in the Device Compatibility
Document.
Wire notification appliances according to the manufacturer's instructions.
Maximum current per circuit is 3.0 A. Maximum current per module depends on the type of
power supply (standard or auxiliary).
Canadian installations require model N-ELR End-of-Line Resistor Assembly (Style Y only).
Size NAC wiring so the voltage drop does not exceed the minimum rated voltage of the
notification appliance used as the last device on the circuit.
For zone coded applications, refer to the UZC-256 Universal Zone Coder manual.
The ICM-4RK is California Code programmable (microprocessor P/N 34077 Rev. B or
higher). To program for California Code, cut diode D35 as shown in Figure 3.23. (See
appendix section of the Programming Manual for more detail.)
Figure 3.23 Location of D35 on ICM-4RK Circuit Board
48
Typical NFPA
Style Y (Class B) NAC
4.7K,
1/2 watt ELR
P/N 71252
UL-listed 24 VDC
Polarized Devices
unused circuits
B+ A+ A– B– B+ A+ A– B–
Figure 3.22 Field-Wiring an ICM-4RK/ICE-4
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
Typical NFPA
Style Z (Class A) NAC
Jumpers for
B+ A+ A– B– B+ A+ A– B–
Cut D35 on the circuit board to
produce California code.
Installing Panel Circuit Modules
Jumpers for
unused circuits