Error codes – Recommended
action
69
Potentiometer
parameters
Additional indication at
the fault alarm contact
Status classification
Recommended action Confirm error, perform a reset and re-initialize the positioner.
70
Calibration
Additional indication at
the fault alarm contact
Status classification
Recommended action Return device to SAMSON for repair.
71
General
parameters
Status classification
Recommended action Confirm error. Check and, if necessary, change the settings of the
73
Internal device
error 1
Status classification
Recommended action Return device to SAMSON for repair.
74
HART
parameters
®
Status classification
Recommended action Confirm error.
16-16
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Error in digital potentiometer parameters
[Maintenance required]
Error in data from production calibration. The positioner continues
operation with cold start values.
[Maintenance required]
Error in parameters not critical to control operation.
[Maintenance required]
required parameters.
Internal device error
[Maintenance required]
Error in parameters not critical to control operation.
[Maintenance required]
Check and, if necessary, change the settings of the required parameters.
EB 8384-3 EN