7.5.3
MAN – Initialization based on a manually selected OPEN
position
Before starting initialization, move the control valve manually to the OPEN position. Turn the
rotary pushbutton (
cally increasing signal pressure. The positioner calculates the differential travel/angle from
the OPEN and CLOSED positions and adopts it as the operating range with limits of lower
travel/angle range value (Code 8) and upper travel/angle range value (Code 9).
Enable configuration:
Configuration is locked again if no settings are entered within 120 seconds.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Enter the pin position:
1. Turn
until Code 4 appears.
2. Press
, the code number 4 blinks.
3. Turn
to select pin position on lever (see
relevant section on attachment).
4. Press
to confirm.
Select the initialization mode:
1. Turn
until Code 6 appears.
2. Press
, the code number 6 blinks.
3. Turn
until MAN appears.
4. Press
to confirm the MAN initialization
mode.
EB 8384-3 EN
) clockwise in small steps. The valve must be moved with a monotoni-
Start-up and configuration
Enable configuration
Default: No
Pin position
Default: No
mm
Init mode
Default: MAX
7-11