Error appendix
Error codes – Recommended
action
65
Hardware
Additional indication at
the fault alarm contact
Status classification
Recommended action Confirm error and return to automatic mode or perform a reset and
66
Data memory
Additional indication at
the fault alarm contact
Status classification
Recommended action Return device to SAMSON for repair.
67
Check calculation
Additional indication at
the fault alarm contact
Status classification
Recommended action Confirm error. If this is not possible, return the device to SAMSON for
Data errors
Error codes – Recommended
action
68
Control parameters
Additional indication at
the fault alarm contact
Status classification
Recommended action Confirm error, perform a reset and re-initialize the positioner.
EB 8384-3 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Initialization key jammed (firmware version R 1.51 and higher)
A hardware error has occurred. The positioner changes to the fail-safe
position (SAFE).
[Maintenance alarm]
re-initialize the positioner. In the problem still persists, return device to
SAMSON for repair.
No more data can be written to the memory, e.g. because written data
deviate from read data. The valve moves to the fail-safe position.
Maintenance alarm (cannot be classified)
Hardware controller monitored by test calculation.
[Maintenance alarm]
repair.
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Error in control parameters.
[Maintenance required]