Start-up and configuration
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Enter the pin position and nominal range:
1. Turn
until Code 4 appears.
2. Press
, the code number 4 blinks.
3. Turn
to select pin position on lever (see
relevant section on attachment).
4. Press
to confirm.
5. Turn
until Code 5 appears.
6. Press
, the code number 5 blinks.
7. Turn
and set rated travel of the valve.
8. Press
to confirm.
Select the initialization mode:
1. Turn
until Code 6 appears.
2. Press
, the code number 6 blinks.
3. Turn
until NOM appears.
4. Press
to confirm the NOM initialization
mode.
Start initialization:
Î Press INIT key.
Î After the initialization has been successfully completed:
Check the direction of action (Code 7) and, if necessary, change it.
7-10
Enable configuration
Default: No
Pin position
Default: No
mm
Nominal range
(locked when Code 4 =
No)
mm
Init mode
Default: MAX
EB 8384-3 EN