Samson 3730 Series Mounting And Operating Instructions page 196

Table of Contents

Advertisement

Code
Parameter – Readings/
no.
values [default setting]
32* Error message in case of
'Function check' con-
densed state
[YES], No, ESC
33* Error message in case of
condensed state 'Mainte-
nance required'
[YES], No, ESC
34* Closing direction
CL, [CCL], ESC
35* Blocking position
[0.0] mm/° /%, ESC
36* Reset
[No], Std, diAG, ESC
37* Position transmitter
No, YES
38* Inductive alarm
[No], YES, ESC
16-8
Description
YES:
Error message also in case of 'Function check' condensed
state
No:
'Function check' condensed state does not cause an error
message to be issued
Regardless of the condensed state, the fault alarm output always
switches when the error codes 57, 58, 60, 62 and 64 to 70, 76 are
issued.
YES:
Error message only in case of condensed state
'Maintenance alarm' and 'Maintenance required'
No:
Error message only in case of condensed state
'Maintenance alarm'
Regardless of the condensed state, the fault alarm output always
switches when the error codes 57, 58, 60, 62 and 64 to 70, 76 are
issued.
CL:
Clockwise
CCL:
Counterclockwise
Direction of rotation to reach the valve's CLOSED position (view onto
rotary switch with positioner cover open).
Needs only be entered in SUb initialization mode (Code 6).
Enter the blocking position (distance to CLOSED position)
Only necessary with SUb initialization mode.
Std:
Resets all parameters and diagnosis data to their default
settings. After a reset, the positioner must be re-initialized.
diAG: Resets diagnosis data only. Plotted reference graphs and
logs remain saved.
The positioner does not need to be re-initialized.
Read only
Indicates whether an optional position transmitter is installed.
Indicates whether the inductive limit switch option is installed or not.
EB 8384-3 EN