Code
Parameter – Readings/
no.
values [default setting]
28* Alarm test
Reading direction:
Standard
[No]
RUN 1
RUN 2
RUN 3
ESC
29* Position transmitter x/ix
[ää], äæ, ESC
30* Fault alarm ix
HI, LO, [No], ESC
31* Position transmitter test
–10.0 to 110.0 % of the
operating range, [default
value is last indicated val-
ue of the position transmit-
ter], ESC
Analog position transmitter: Code 29/30/31 can only be selected if the position transmitter (optional) is installed.
3)
EB 8384-3 EN
Description
Test of software limit switch alarms A1 and A2 as well as of fault
alarm contact A3.
If the test is activated, the contact is switched five times.
Turned
RUN 1/1 RUN: software limit switch A1 to ≥2.2 mA
[No]
RUN 2/2 RUN: software limit switch A2 to ≥2.2 mA
1 RUN
2 RUN
RUN 3/3 RUN: fault alarm contact A3 to ≤1.0 mA
3 RUN
ESC
Operating direction of the position transmitter: it indicates assign-
3)
ment between travel/angle position and output signal i based on
CLOSED position.
The operating range (see Code 8) of the valve is represented by the
4 to 20 mA signal. Values exceeding or falling below the limits 2.4
and 21.6 mA can be indicated.
When the positioner has not been mounted (set point smaller than
3.6 mA), the signal is 0.9 mA and 3.8 mA the positioner has not
been initialized. When YES is set in Code 32, the position transmit-
ter issues the value as per Code 30 during initialization or zero cali-
bration. When No is set in Code 32, 4 mA is issued during a run-
ning calibration.
Select if and how alarms that cause the fault alarm contact to be
3)
switched are also indicated by the position transmitter.
HI ix =21.6 ±0.1 mA or LO ix =2.4 ±0.1 mA
Testing the position transmitter. Values can be entered in relation to
3)
the operating range.
The momentary valve position is used in initialized positioners local-
ly as the start value (bumpless changeover to the test mode). When
testing by software, the entered simulation value is issued as the po-
sition feedback signal for 30 seconds.