Model Number Descriptions; Unit Model Number - Trane CVHE Installation Instructions Manual

E-frame upgrade adaptive frequency drive for tracer adaptiview centrifugal chiller controllers
Table of Contents

Advertisement

Model Number Descriptions

Unit Model Number

For service purposes, Trane
AFDH Air-Cooled drive upgrade
packages are assigned a multiple
character alphanumeric model
number that precisely identifies each
unit.
An explanation of the identification
code that appears on the unit
nameplate is shown below. Use of
the service model number will
enable the owner/operator, installing
contractors, and service technicians
to define the operation, components,
and options for any specific unit.
Refer to the model number printed
on the nameplate when ordering
replacement parts or requesting
service.
Digits 1, 2, 3 — Air Cooled
Adaptive Frequency Drive
AFD = Air Cooled Adaptive Frequency
Drive
Digit 4 — Development
Sequence
H
Digits 5, 6, 7, 8 — Starter Size
(Performance RLA rating)
Performance RLA = Performance RLA
Digit 9 — Chiller Voltage
D
=
380V 60 Hz 3 Phase
E
=
440V 60 Hz 3 Phase
F
=
460V 60 Hz 3 Phase
G
=
480V 60 Hz 3 Phase
H
=
575V 60 Hz 3 Phase
J
=
600V 60 Hz 3 Phase
R
=
380V 50 Hz 3 Phase
T
=
400V 50 Hz 3 Phase
U
=
415V 50 Hz 3 Phase
Digits 10, 11— Design Sequence
** =
Factory assigned
Digit 12 — New Short Circuit
Rating
C
=
35K Short Circuit
A
=
65K Short Circuit
B
=
100K Short Circuit
Digits 13, 14 — Maximum RLA
1B =
190 Maximum RLA - 60 Hz
(460/480)
1C =
240 Maximum RLA - 60 Hz
(460/480)
0C =
302 Maximum RLA - 60 Hz
(460/480)
0D =
361 Maximum RLA - 60 Hz
(460/480)
0E =
443 Maximum RLA - 60 Hz
(460/480)
AFDH-SVN004C-EN
1A =
535 Maximum RLA - 60 Hz
(460/480)
0H =
590 Maximum RLA - 60 Hz
®
Model
(460/480)
0J =
678 Maximum RLA - 60 Hz
(460/480)
0K =
730 Maximum RLA - 60 Hz
(460/480)
01 =
780 Maximum RLA - 60 Hz
(460/480)
02 =
890 Maximum RLA - 60 Hz
(460/480)
1D =
131 Maximum RLA - 60 Hz
(575/600)
1E =
155 Maximum RLA - 60 Hz
(575/600)
1F =
192 Maximum RLA - 60 Hz
(575/600)
0L =
242 Maximum RLA - 60 Hz
(575/600)
0M =
290 Maximum RLA - 60 Hz
(575/600)
0N =
344 Maximum RLA - 60 Hz
(575/600)
0P =
400 Maximum RLA - 60 Hz
(575/600)
0R =
450 Maximum RLA - 60 Hz
(575/600)
0T =
500 Maximum RLA - 60 Hz
(575/600)
0U =
570 Maximum RLA - 60 Hz
(575/600)
0V =
630 Maximum RLA - 60 Hz
(575/600)
03 =
729 Maximum RLA - 60 Hz
(575/600)
04 =
850 Maximum RLA - 60 Hz
(575/600)
1G =
212 Maximum RLA - 50 Hz
(380/400)
1H =
260 Maximum RLA - 50 Hz
(380/400)
0W =
315 Maximum RLA - 50 Hz
(380/400)
0X =
395 Maximum RLA - 50 Hz
(380/400)
0Y =
480 Maximum RLA - 50 Hz
(380/400)
0Z =
588 Maximum RLA - 50 Hz
(380/400)
05 =
658 Maximum RLA - 50 Hz
(380/400)
06 =
745 Maximum RLA - 50 Hz
(380/400)
07 =
800 Maximum RLA - 50 Hz
(380/400)
08 =
880 Maximum RLA - 50 Hz
(380/400)
09 =
990 Maximum RLA - 50 Hz
(380/400)
Digit 15 — Chiller Control Type
3
=
AdaptiView Controls Only
Digit 16 — Agency Listing
1
=
UL Listing (includes Canada and
California)
0
=
No Listing
Digit 17 — AFD Type
C
=
NEMA 1 Upgrade Enclosure
Digit 18 — Mounting Type
C
=
Remote Mount
A
=
Transition Mount
L
=
LiquiFlo Mount
P
=
Direct Mount 440E, 5000, 5800
Frame
T
=
Direct Mount 400 Frame
Digit 19 — AFD to Motor
Transition
0
=
No Motor Transition
A
=
6" Sheetmetal Transition
C
=
12" Sheetmetal Transition
B
=
18" Sheetmetal Transition
Digit 20 — Frame Size
D
=
D - Frame
E
=
E - Frame
Digit 21 — Evaporator Shell Size
0
=
For Transition, LiquiFlo, or
Remote
5
=
050S Short Evaporator Shell
6
=
050L Long Evaporator Shell
7
=
080S Short Evaporator Shell
8
=
080L Long Evaporator Shell
A
=
142E Extended Evaporator Shell
B
=
142M Medium Evaporator Shell
C
=
142L Long Evaporator Shell
E
=
210L Long Evaporator Shell
Digit 22 — Replacement Bracket
for LF1.0/LF1.5
0
=
No Bracket Needed
1
=
Replacement Bracket Kit Needed
Digit 23
0
Digit 24 — Lug Sizes
0
=
All Applicable Lugs
N
=
Two Wire 3/0 - 250 KCmil
B
=
Two Wire 400 - 500 KCmil
C
=
Four Wire 4/0 - 400 KCmil
D
=
Three Wire 4/0 - 400 KCmil
E
=
Three Wire 500 - 750 KCmil
F
=
Two Wire 2/0 - 250 KCmil
G
=
One Wire 2/0 - 500 KCmil
H
=
Three Wire 3/0 400 KCmil
J
=
Two Wire 500 - 750 KCmil
K
=
One Wire 200 - 500 KCmil
L
=
Two Wire 3/0 - 350 KCmil
M =
Two Wire 2AWG - 500 KCmil
P
=
Three Wire 4/0 - 500 KCmil
Q
=
Four Wire 4/0 - 500 KCmil
R
=
Four Wire 3/0 - 400 KCmil
Digit 25 — Jumper Bar Kit
0
=
No Jumper Bars Required
A
=
Bar Kit 1 (distance between holes
5.385 and dia. .812)
B
=
Bar Kit 2 (distance between holes
5.831 and dia. .812)
C
=
Bar Kit 3 (distance between holes
6.103 and dia. .812)
D
=
Bar Kit 4 (distance between holes
6.103 and dia. 1.187)
E
=
All Bars Included
Digits 26, 27 — Design Specials
00 =
No Design Special
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

CvhfAfdh

Table of Contents