Required Reprogramming Of Tracer® Adaptiview™ Controls; Reprogramming Factory Installed Tracer® Adaptiview™ Controls (Ctv Simplex Firmware) - Trane CVHE Installation Instructions Manual

E-frame upgrade adaptive frequency drive for tracer adaptiview centrifugal chiller controllers
Table of Contents

Advertisement

Installation
1.
Factory installed wiring
2.
Field installed wiring
3.
Actual wire designators may vary depending upon the specific model/version of chiller control that the AFDH drive is being linked with.
Note:
Please refer to the original chiller control wiring diagrams and the wire descriptions listed in Figure Callouts 4–11 if an actual wire designator
does not match the one shown in this graphic.
4.
115VAC feed to chiller control panel
5.
Neutral feed to chiller control panel
6.
Normally Closed terminal(2) on HPC (High Pressure Cutout) switch (3S1) for original chiller with starter module and/or non-comm. Drive
terminal 4 is 115VAC only.
Note: For original chillers with a communicating drive, high pressure cutout wiring is 24V. For original chillers with a starter module, high pressure cutout
wiring is 115V.
7.
From 1A7 J2-4 oil pump LLID
8.
From 1A7 J2-2 oil LLID or could come from the 1X1 terminal block
9.
and 10. Normal closed terminal on HPC switch (3S1) for original chiller with comm. Drive terminals 9 and 10 are 24VDC only.
Note: For original chillers with a communicating drive, high pressure cutout wiring is 24V.
11. 12. and 13
From UC800 IMC Modbus link
.
Important:
If the chiller does not already have a
condenser pressure transducer. Do not
forget to install the condenser pressure
transducer provided in the Tracer®
AdaptiView™ Miscellaneous Hardware
Package. The accurate pressure readings
required by the chiller controls to enable the
most efficient operation of the chiller with
the upgraded AFDH drive can only be
effectively measured with a pressure
transducer.
Table 26. UC800/Tracer® AdaptiView™ CTV parameter values with upgrade AFDH
Tracer TU Service Setpoints View:
Adjustable Frequency Drive Setpoints
AF Control
ReOptimization Sensitivity
Tracer TU Field Startup View:
Adjustable Frequency Drive
AFD Temperature Limit Setpoint
Maximum Frequency
Minimum Frequency
Surge Speed Increase
Tracer TU Configuration View: Main
Unit Type (MODL)
Tracer TU Configuration View: UC800
Starter Type
Impeller Diameter (CPIM)
Tracer TU Configuration View: Starter
Unit Line Voltage
Motor NP Power
Motor Temperature Protection Type
50
Required Reprogramming of
Tracer® AdaptiView™ Controls.
Reprogramming Factory Installed Tracer®
AdaptiView™ Controls (CTV Simplex
Firmware)
Important:
Note: CTV MP firmware is always used in factory installed
Range
Auto, Fixed
0–100%
Range
0.0 - 360.0
30–60 Hz
30–60 Hz
0–2 Hz
Range
CVHE, CVHF, CVHG, CVGF
Range
Not Applicable
50-345
Range
180–15000V
4000 kW
75 Ohm@75F, 100 Ohm@ 0C
Make sure your laptop is loaded with the
most current version of Tracer TU tool
software so that you have the most up-to-
date version of CTV MP firmware available
to install into the UC800.
Tracer® AdaptiView™ control systems or in
Tracer® AdaptiView™ display upgrades to factory
installed CH530 control systems.
Default Setting
Auto
20
Default Setting
212.0
60
38
1
Default Setting
Enter Chiller Model from Unit Nameplate
CVHE
(Note: only CVHE or CVHF apply)
Default Setting
Unit Mount Wye-Delta
275
Enter CPIM from Unit Nameplate
Default Setting
460
400
75 ohm
Recommended Setting
Auto
20
Recommended Setting
212.0
60
38
1
Recommended Setting
Recommended Setting
TR200 Modbus AFD
Recommended Setting
Enter from Unit Nameplate
Enter from Unit Nameplate
75 ohm
AFDH-SVN004C-EN