Interrupts/diagnostic messages
5.2 Diagnostic messages
Table 5- 5
Diagnostic alarms, their meaning and remedies
Diagnostic alarm
Error
code
Error
9
H
Load voltage
11
H
missing
Hardware interrupt
16
H
lost
Module
1F
H
temporarily
unavailable
Internal error
100
Watchdog tripped.
103
Module is
defective.
Short circuit or
10E
overload at
external encoder
supply
Error at digital
10F
outputs
Faulty external
110
auxiliary voltage
Illegal A/B signal
500
ratio
44
Meaning
Internal module error occurred
Possible cause: Technology module
defective
No technology module L+ supply voltage
Technology module cannot send an
interrupt because a previous interrupt has
not been processed
Possible causes:
Parameter assignment error
Too many hardware interrupts in too
short a time
No normal operation of the technology
module possible
Possible cause: Technology module is
performing a firmware update
Technology module defective
H
Firmware error
H
Technology module defective
Error at encoder supply
H
Possible causes:
Short circuit
Overload
Error at the digital outputs
H
Possible causes:
Short circuit
Overload
Error at supply voltage L+
H
Possible causes:
Low voltage
Wiring of L+ supply voltage defective
Time profile of signals A and B of the
H
incremental encoder does not meet
certain specifications
Possible causes:
Signal frequency too high
Encoder faulty
Process wiring faulty
To correct or avoid errors
Replace technology module
Check BaseUnit type
Check the wiring of the supply voltage
L+ on the BaseUnit
Change interrupt processing in the CPU
and re-assign technology module
parameters correspondingly
Wait until technology module is available
again
Replace technology module
Run firmware update
Replace technology module
Check encoder wiring
Check consumers connected to encoder
supply
Check wiring at the digital outputs
Check consumers connected to the
digital outputs
Check the L+ supply voltage
Check the wiring of the supply voltage
L+ on the BaseUnit
Check process wiring
Check encoder/sensor
Check parameter assignment
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)