Configuring/address space
4.4 Parameters
Parameter setting via ...
Hardware configuration using GSD
file for distributed operation on the
PROFINET IO
Hardware configuration using GSD
file for distributed operation on the
PROFIBUS DP
The parameters are listed in the following tables.
Parameters of the TM PosInput 1 with incremental or pulse encoder
If you use an incremental or pulse encoder, you can set the following parameters:
Table 4- 4
Configurable parameters and their defaults
Parameter
Operating mode
Interface standard
Reaction to CPU STOP
1
Enable additional diagnostic
interrupts
Enabling diagnostic interrupts for
wire break
2
30
Basic procedure
1. Install the latest PROFINET GSD file.
2. Set the parameters of the PROFINET GSD file in the
3. Download the parameter assignment to the module.
1. Install the latest PROFIBUS GSD file.
2. Set parameters of the PROFIBUS GSD file in the
3. Download the parameter assignment to the module.
Value range
Counting
•
Measuring
•
RS422, symmetrical
•
TTL (5 V), asymmetric
•
Output substitute value
•
Keep last value
•
Continue operation
•
Deactivated
•
Activated
•
Deactivated
•
Activated
•
You will then find the module in the Hardware catalog
under "Other field devices".
hardware configuration.
You will then find the module in the Hardware catalog
under "Other field devices".
hardware configuration.
The following tables with
configured in the PROFIBUS GSD file.
This will download the parameters marked with
following tables with the default setting. You can change
these parameters in the user program using data record
128 (Page 58).
Default setting
Counting
RS422, symmetrical
Output substitute value
Deactivated
Deactivated
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
highlighted parameters are not
1
in the
1
Re-
configuration
in RUN
No
Yes
Yes
Yes
Yes
Manual, 02/2014, A5E33015755-AA