Siemens SIMATIC ET 200SP Manual page 39

Technology module tm poslnput 1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Offset to the start
Parameter
address
Byte 8
LD_SLOT_1*
Byte 9
EN_CAPTURE
EN_SYNC_DN
EN_SYNC_UP
SET_DQ1
SET_DQ0
TM_CTRL_DQ1
TM_CTRL_DQ0
SW_GATE
Byte 10
SET_DIR
RES_EVENT
RES_ERROR
Byte 11
*
If values are loaded simultaneously via LD_SLOT_0 and LD_SLOT_1, the first value is taken internally from Slot 0 and
then the value from Slot 1 is taken. This may lead to unexpected intermediate states.
Technology module TM PosInput 1 (6ES7138-6BA00-0BA0)
Manual, 02/2014, A5E33015755-AA
Meaning
Specifies the significance of the value in Slot 1
Bit 7
Bit 6
Bit 5
0
0
0
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
to
1
1
1
Bit 7: Capture function enable
Bit 6: Enable synchronization down (with incremental encoder or pulse encoder)
Bit 5: Enable synchronization up (with incremental encoder or pulse encoder)
Bit 4: Set DQ1
Bit 3: Set DQ0
Bit 2: Enable technological function DQ1
Bit 1: Enable technological function DQ0
Bit 0: Software gate (with incremental encoder or pulse encoder)
Bit 7: Count direction (for encoders without direction signal)
Bits 2 to 6: Reserve; bits must be set to 0
Bit 1: Reset of saved events
Bit 0: Reset of saved error states
Bits 0 to 7: Reserve; bits must be set to 0
4.5 Control and feedback interface
Bit 4
0
No action, idle
1
Load count value (with incremental or pulse
encoder)
0
Reserve
1
Load Start value (with incremental encoder or
pulse encoder)
0
Load comparison value 0
1
Load comparison value 1
0
Load Low counting limit (with incremental
encoder or pulse encoder)
1
Load High counting limit (with incremental
encoder or pulse encoder)
0
Reserve
1
Configuring/address space
39