SYSTEM DATA

(For 0 to 4,500 feet altitude)
Orifice Sizes:
Burner
Natural Gas
Burner
Propane
Max. Input Rating
Natural Gas
32,000 Btu/h
Propane
29,000 Btu/h
Min. Input Rating
Natural Gas
21,000 Btu/h
Propane
23,000 Btu/h
Supply Pressure
Natural Gas
min.
max.
Propane
min.
max.
Manifold Pressure High
Natural Gas
3.5" w.c.
Propane
10" w.c.
Manifold Pressure Low
Natural Gas
1.6" w.c.
Propane
6.4" w.c.
Electrical: 115V_60 Hz less than 2 amp
Circulation Fan: 75/125 CFM.
Log Set: Ceramic fiber, 4 per set.
Output capacity:
The efficiency rating of the appliance is a
product thermal efficiency rating determined
under continuous operating conditions and
was determined independently of any installed
system.

GAS CONNECTION

The gas connection is a 3/8" x 18" long flexible pipe.
This is supplied and installed at the left rear of the
unit. See "Unit Dimensions" section for Diagram.
#36
The gas line can be rigid pipe or to make installation
#52
easier, use a listed flexible connector and manual
shutoff valve if allowed by local codes, or copper
if approved. For minimum and maximum supply
pressure see the System Data table.
Note: During any pressure testing of the gas
supply piping system that exceeds test
pressures of 1/2 psig, this appliance
and its individual shutoff valve must be
disconnected from the piping system. If
test pressures equal to or less than 1/2
5.0" w.c
psig are used then this appliance must
14.0" w.c.
be isolated from the piping system by
11.0" w.c.
closing its individual manual shutoff
14.0" w.c.
valve during the testing.

HIGH ELEVATION

This unit is approved in Canada for altitude 0 to
4500 ft. (CSA 2.17-2017) with the orifice supplied.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" (# 7) and/or "OUT" (# 7) pres-
3. Attach manometer to "IN" and/or "OUT" pres-
4. Light the pilot and turn the valve to "ON" posi-
5. The pressure check should be carried out with
7. When finished reading manometer, turn off the
Regency
CLASSIC™ C34-11 Direct Vent Freestanding Gas Stove
®
installation
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
sure tap(s), turning counterclockwise with a 1/8"
wide flat screwdriver.
sure tap(s) using a 5/16" ID hose.
tion.
the unit burning and the setting should be within
the limits specified on the safety label.
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Screw should be snug, but do not over tighten.
|
35
|