DESCRIPTION
Motor Temp Override
Cond Pressure Override
Refrig Override Delta T
Chilled Medium
Brine Refrig Trippoint
Compr Discharg Alert
Bearing Temp Alert
Water Flow Verify Time
Oil Press Verify Time
Water/Brine Deadband
Recycle Restart Delta T
Surge Limit/HGBP Option
Surge=0/HGBP=1
Surge/HGBP Delta T1
Surge/HGBP Delta P1
Surge/HGBP Delta T2
Surge/HGBP Delta P2
Surge/HGBP Deadband
Surge Delta Percent Amps
Surge Time Period
Demand Limit Source
Amps=0/Load=1
Amps Correction Factor
NOTE: Values in [ ] indicate HFC-134a values, if this refrigerant is configured in the Control Test.
19XL PIC SERVICE1 TABLE CONFIGURATION SHEET
RANGE
150 to 200
(66 to 93)
150 to 245
(1034 to 1639)
[90 to 200 (620 to 1379)]
2 to 5
(1 to 3)
Water/Brine
8 to 40
(–13.3 to 4)
125 to 200
(52 to 93)
175 to 185
(79 to 85)
0.5 to 5
15 to 300
0.5 to 2.0
(0.3 to 1.1)
2.0 to 10
(1.1 to 5.5)
0/1
0.5 to 15
(0.3 to 8.3)
50 to 170
(345 to 1172)
[30 to 170 (206 to 1172)]
0.5 to 15.0
(0.3 to 8.3)
50 to 170
(345 to 1172)
[30 to 170 (206 to 1172)]
1 to 3
(0.6 to 1.6)
10 to 50
1 to 5
0/1
1 to 8
UNITS
DEG F
(DEG C)
psig
(kPa)
DEG F
(DEG C)
DEG F
(DEG C)
DEG F
(DEG C)
DEG F
(DEG C)
MIN
SEC
DEG F
(DEG C)
DEG F
(DEG C)
DEG F
(DEG C)
psi
(kPa)
DEG F
(DEG C)
psi
(kPa)
DEG F
(DEG C)
%
MIN
CL-7
DEFAULT
VALUE
200
(93)
195
(1345)
[125 (862)]
3
(1.6)
Water
33
(1)
200
(93)
175
(79)
5
15
1.0
(0.6)
5
(2.8)
0
1.5
(0.8)
75
(517)
[50 (345)]
10
(5.6)
170
(1172)
[85 (586)]
1
(0.6)
25
2
0
3