Carrier PC211 Start-Up, Operation And Maintenance Instructions Manual page 278

Hermetic centrifugal liquid chillers with hcfc–22 and hfc–134a
Table of Contents

Advertisement

Table 6 — Potentiometer Adjustment
Dial
Starting Current
Ramp Time (Adjust-
able Current Ramp)
Current Limit
Pulse Start
Current Trip
Power Saver
CCW — Counterclockwise
CW — Clockwise
Adjustment Range
Minimum
Maximum
(CCW)
(CW)
100%
400%
2 seconds
30 seconds
100%
400%
0 (Off)
2 seconds
50%
400%
Function
Sets initial starting current
level.
Sets time during which cur-
rent ramps from the initial
starting level to the maxi-
mum possible current limit
setting.
Sets maximum starting cur-
rent.
Sets duration of 400% cur-
rent pulse. Pulse is used to
break load free.
Sets running current trip.
Factory Setting
100%
15 seconds
250%
OFF
175%
OFF