Carrier PC211 Start-Up, Operation And Maintenance Instructions Manual page 126

Hermetic centrifugal liquid chillers with hcfc–22 and hfc–134a
Table of Contents

Advertisement

absolute pressure manometer or wet-bulb vacuum indicator
500 v insulation tester (megohmmeter) for compressor motors with nameplate volt-
age of 600 v or less, or a 5000-v insulation tester for compressor motor rated above
600 v
Using the Optional Storage Tank and Pumpout System
Refer to
Pumpout and Refrigerant Transfer Procedures
preparation, refrigerant transfer, and machine evacuation.
Remove Shipping Packaging
Remove any packaging material from the control center, power panel, guide vane actuator,
motor cooling and oil reclaim solenoids, motor and bearing temperature sensor covers, and the
factory-mounted starter.
Click here for Figure 25 — Typical Wet-Bulb Type Vacuum Indicator
Open Oil Circuit Valves
Check that the oil filter isolation valves
checking the valve stem.
Torque All Gasketed Joints
Gaskets normally have relaxed by the time the machine arrives at the jobsite. Tighten all
gasketed joints to ensure a leak tight machine.
section for: pumpout system
(Figure
4) are open by removing the valve cap and
(Figure
25)