Carrier PC211 Start-Up, Operation And Maintenance Instructions Manual page 134

Hermetic centrifugal liquid chillers with hcfc–22 and hfc–134a
Table of Contents

Advertisement

WARNING
Do not start or megohm test the compressor motor or oil pump motor, even for a
rotation check, if the machine is under dehydration vacuum. Insulation break-
down and severe damage may result.
Dehydration is readily accomplished at room temperatures. Use of a cold trap
may substantially reduce the time required to complete the dehydration. The higher the room
temperature, the faster dehydration takes place. At low room temperatures, a very deep
vacuum is required for boiling off any moisture. If low ambient temperatures are involved,
contact a qualified service representative for the dehydration techniques required.
Perform dehydration as follows:
1. Connect a high capacity vacuum pump (5 cfm [.002 m
refrigerant charging valve
should be as short and as large a diameter as possible to provide least resistance to gas
flow.
2. Use an absolute pressure manometer or a wet bulb vacuum indicator to measure the
vacuum. Open the shutoff valve to the vacuum indicator only when taking a reading. Leave
the valve open for 3 minutes to allow the indicator vacuum to equalize with the machine
vacuum.
!
WARNING
(Figure 2A
or
Figure
3
/s] or larger is recommended) to the
2B). Tubing from the pump to the machine
(Figure
29)