Carrier PC211 Start-Up, Operation And Maintenance Instructions Manual page 260

Hermetic centrifugal liquid chillers with hcfc–22 and hfc–134a
Table of Contents

Advertisement

Table 2, Example 7 — Service1 Display Screen (Continued)
Description
Surge/HGBP Delta P2
Full Load Points (T2/P2)
Surge/HGBP Deadband
Surge Delta Percent Amps
Surge Time Period
Demand Limit Source
Select: Amps=0, Load=1
Amps Correction Factor
Motor Rated Load Amps
Motor Rated Line Voltage
Meter Rated Line KW
Line Frequency
Select: 0=60 Hz, 1=50 Hz
Compr Starter Type
Condenser Freeze Point
Soft Stop Amps Threshold
Note:
1. Condenser Freeze Point and Softstop Amps Threshold are only selectable/readable on PSIO Software
Versions 09 and higher.
2. Values in [ ] indicate HFC-134a values.
3.
= delta degrees.
Configurable
Range
[30-170 (207-1172)]
1-3 (0.6-1.6)
10-50
1-5
0/1
1-8
1-9999
1-9999
1-9999
0/1
REDUCE/FULL
–20-35 (–28.9-1.7)
40-100
Reference
Units
Point
Name
PSI (kPa)
hgb dp2
hgb dp
DEG F (DEG C)
%
surge a
MIN
surge t
dem src
corfact
AMPS
a fs
VOLTS
v fs
kW
kw fs
HZ
freq
starter
DEG F (DEG C)
cdfreeze
%
softstop
Default Value
170 (1172) [85 (586)]
1 (0.6)
25
2
0
3
200
460
600
0
REDUCE
34 (1)
100