Table 2, Example 1 — Status01 Display Screen (Continued)
Description
Entering Chilled Water
Leaving Chilled Water
Entering Condenser Water
Leaving Condenser Water
Evaporator Refrig Temp
Evaporator Pressure
Condenser Refrig Temp
Condenser Pressure
Discharge Temperature
Bearing Temperature
Motor Winding Temp
Oil Sump Temperature
Oil Pressure Transducer
Oil Pressure
Line Voltage: Percent
Actual
*Remote Contacts Input
Total Compressor Starts
Starts in 12 Hours
Compressor Ontime
*Service Ontime
*Compressor Motor kW
Note: All values are variables available for read operation to a CCN. Descriptions shown with (*) support
write operations for BEST programming language, data-transfer, and overriding.
Range
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–40-245 (–40-118)
–6.7-420 (–46-2896)
–6.7-420 (–46-2896)
0-999
0-9999
Off/On
0-65535
0-8
0-500000.0
0-32767
0-9999
Reference Point
Units
Name (Alarm
History)
DEG F (DEG C)
ECW
DEG F (DEG C)
LCW
DEG F (DEG C)
ECDW
DEG F (DEG C)
LCDW
DEG F (DEG C)
ERT
PSI (kPa)
ERP
DEG F (DEG C)
CRT
PSI (kPa)
CRP
DEG F (DEG C)
CMPD
DEG F (DEG C)
MTRB
DEG F (DEG C)
MTRW
DEG F (DEG C)
OILT
PSI (kPa)
OILP
PSID (kPad)
OILPD
%
V P
VOLTS
V A
REMCON
c starts
STARTS
c hrs
HOURS
HOURS
S HRS
kW
CKW