Carrier PC211 Start-Up, Operation And Maintenance Instructions Manual page 257

Hermetic centrifugal liquid chillers with hcfc–22 and hfc–134a
Table of Contents

Advertisement

Example 5 — Configuration (Config) Display Screen
To access this display from the LID default screen:
1. Press MENU.
2. Press SERVICE.
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT.
5. Scroll down to highlight CONFIG.
6. Press SELECT.
Table 2, Example 5 — Configuration (Config) Display Screen
Description
RESET TYPE 1
Degrees Reset at 20 mA
RESET TYPE 2
Remote Temp (No Reset)
Remote Temp (Full Reset)
Degrees Reset
RESET TYPE 3
CHW Delta T (No Reset)
CHW Delta T (Full Reset)
Degrees Reset
Select/Enable Reset Type
ECW CONTROL OPTION
Demand Limit At 20 mA
20mA Demand Limit Option
Auto Restart Option
Remote Contacts Option
Temp Pulldown Deg/Min
Load Pulldown %/Min
Select Ramp Type:
Temp = 0, Load = 1
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
CCN Occupancy Config:
Schedule Number
Broadcast Option
ICE BUILD Option
ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both
ICE BUILD Recycle Option
Note:
= delta degrees.
Configurable
Range
–30-30 (–17-17)
–40-245 (–40-118)
–40-245 (–40-118)
–30-30 (–17-17)
0-15 (0-8)
0-15 (0-8)
–30-30 (–17-17)
0-3
DISABLE/ENABLE
40-100
DISABLE/ENABLE
DISABLE/ENABLE
DISABLE/ENABLE
2-10
5-20
0/1
0-99
0-60
0-120
3-99
DISABLE/ENABLE
DISABLE/ENABLE
0-2
DISABLE/ENABLE
Reference
Units
Point Name
DEG F (DEG C)
deg 20ma
res rt1
DEG F (DEG C)
DEG F (DEG C)
res rt2
DEG F (DEG C)
res rt
DEG F (DEG C)
restd 1
restd 2
DEG F (DEG C)
DEG F (DEG C)
deg chw
res sel
ecw opt
%
dem 20ma
dem sel
astart
r contact
tmp ramp
kw ramp
ramp opt
ldsgrp
%
ldsdelta
MIN
maxldstm
occpcxxe
occbrcst
ibopt
ibterm
ibrecyc
Default
Value
10 (6 )
85 (29)
65 (18)
10 (6 )
10 (6 )
0 (-0 )
5 (3 )
0
DISABLE
40
DISABLE
DISABLE
DISABLE
3
10
1
0
20
60
3
DISABLE
DISABLE
0
DISABLE