To Install The Duct Flanges; To Install The Ekvdx Option - Daikin VAM-J8 Series Manual

Heat reclaim ventilation unit
Hide thumbs Also See for VAM-J8 Series:
Table of Contents

Advertisement

14.2.2 To install the duct flanges

14.2.3 To install the EKVDX option

VAM350~2000J8VEB
Heat reclaim ventilation unit
4P664012-1 – 2021.08
c KRP1BA101 (installation box)
d EKMP65VAM (mounting plate)
f Screw
g Screw (supplied with the installation box)
1 Remove the screws from the middle of the plate connecting the 2 units.
2 Attach the optional mounting plate (EKMPVAM) on top of the plate
connecting the 2 units.
3 Attach the optional adapter PCB (KRP2A51) in the installation box
(KRP1BA101).
4 Follow the installation instructions provided with the option kits (BRP4A50A,
KRP2A51 and KRP1BA101).
5 Guide the PCB wire through the dedicated holes and attach it as instructed in
"15.2 Opening the switch
6 Attach the options to the optional mounting plate, as shown in the figure.
7 After the wires are connected, fasten the switch box cover.
1 Position the duct flanges (a) over the duct holes.
2 Secure the duct flanges with the provided screws (b) (see accessory bag).
b
a Duct flange
b Screw
Model
VAM350
VAM500
VAM650
VAM800
VAM1000
VAM1500
VAM2000
See
"17.2 Field
settings" [
For more information, see the Installation and operation manual of the EKVDX.
4
box" [
 54].
a
Required screws
16
16
24
24
24
48
48
4
 72].
14
Unit installation
|
Duct flanges
4× Ø200 mm
4× Ø200 mm
4× Ø250 mm
4× Ø250 mm
4× Ø250 mm
8× Ø250 mm
8× Ø250 mm
Installer and user reference guide
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents