13.4 Combining units and options

13.4.1 Possible options for the heat reclaim ventilation unit

Installer and user reference guide
40
INFORMATION
Certain options may NOT be available in your country.
Adapter PCB
Options BRP4A50A and KRP2A51.
At temperatures below –10°C, it is mandatory to use an electrical pre-heater. This
heater is connected with option PCB BRP4A50A.
CAUTION
If an electrical heater is installed, use non-flammable duct. For safety reasons, be
sure to keep a distance of at least 2  m between the heater and the heat reclaim
ventilation unit.
For model 650: the optional mounting plate (EKMP65VAM) is required.
For models 1500 and 2000: the optional mounting plate (EKMPVAM) is required.
When installing option KRP2A51, the optional installation box (KRP1BA101) is
required.
Filter
This option may be mandatory. Check the local legislation. It is recommended in
places with poor outside air quality.
Install the filter behind the heat exchange element either at the supply air side or
at the exhaust air side. Keep the standard filter in place. Remove the standard filter
ONLY when installing an option filter both in front of and behind the heat exchange
element.
For installation instructions, see the installation manual of the filter kit.
Model
EKAFVJ50F6
EKAFVJ50F7
EKAFVJ50F8
EKAFVJ65F6
EKAFVJ65F7
EKAFVJ65F8
EKAFVJ100F6
EKAFVJ100F7
EKAFVJ100F8
(a)
See the databook for pressure drop curves for each capacity class of unit and each class of
filter.
Pressure drop over the filter
Filter class
350+500
M6
F7
F8
M6
F7
F8
M6
F7
F8
(a)
650
800~2000
VAM350~2000J8VEB
Heat reclaim ventilation unit
4P664012-1 – 2021.08