TABLE 9 - PHYSICAL DATA (YMAA/YMPA0160-0260)
Compressor
Working ambient temp.
Air side heat
exchanger
Working ambient temp.
(without Hydro Kit)
Water side heat
exchanger
Total pressure drop
Working range water
leaving temp. cooling
Working range water
leaving temp. heating
Dimensions
(without Hydro Kit)
Dimensions (with
Hydro Kit)
Weight (without
Hydro Kit)
Weight (with
Hydro Kit)
Notes
1.Each unit is configured with one inverter scroll compressor;
2.The units are tested in compliance with EN14511-3;
3.Unit dimension for base model only.
JOHNSON CONTROLS
Cooke Industries - Phone: +64 9 579 2185
Model
Type
/
Quantity
pcs
Fan Motor Type
/
Fan Qty
pcs
°C
cooling mode
°C
heating mode
Type
/
Unit water volume
L
Pump type
Nominal flow rate
L/s
Flow rate range
L/s
kPa
°C
°C
Overall length
mm
Overall width
mm
Overall height
mm
Overall length
mm
Overall width
mm
Overall height
mm
Shipping weight
kg
Operating weight
kg
Shipping weight
kg
Operating weight
kg
Email: sales@cookeindustries.co.nz
SECTION 5 – TECHNICAL DATA
YMAA/YMPA
0160PE
0200PE
DC inverter scroll and fixed speed scroll
5
6
EC motor
3
3
-17.8~48
-17.8~48
-15~25
-15~25
Brazed Plate Heat Exchanger
27
29
VSD pump
7.4
9.1
3.7~11.1
4.5~13.6
23
29
5~20
5~20
-8~20
-8~20
25~55
25~55
2240
2240
3050
3050
2500
2500
2240
2240
3050
3050
2500
2500
1895
1974
1922
2003
2071
2150
2115
2196
Web: www.cookeindustries.co.nz
0230PE
0260PE
7
8
4
4
-17.8~48
-17.8~48
-15~25
-15~25
32
34
10.5
11.9
5.3~15.8
6.0~17.9
41
38
5~20
5~20
-8~20
-8~20
25~55
25~55
2240
2240
3050
3050
2500
2500
2240
2240
3050
3050
2500
2500
2203
2282
2235
2316
2379
2458
2428
2509
47