SECTION 10 – SERVICE AND TROUBLESHOOTING
TABLE 41 - TROUBLESHOOTING
PROBLEM
No display on HMI.
Unit will not operate.
"Chiller Water Flow"
Fault
"Low Suction Pressure"
Fault
"High Discharge Pressure or
Compressor Overload" Fault
122
Cooke Industries - Phone: +64 9 579 2185

TROUBLESHOOTING

CAUSE
1. No 230VAC to 24VAC Transformer.
2. No 24VAC to Microboard.
3. Control Transformer defective, no
24VAC output.
4. Defective IPU II & I/O Board or the
Display Board.
1. No chilled liquid flow.
2. Too much air in piping system.
3. Flow switch improperly installed.
4. Defective flow switch.
5. Remote cycling device open.
1. Suction service valve not open or valve
defective.
2. Low refrigerant charge.
3. Fouled or clogged BPHE.
4. EEV defective.
5. Reduced flow of chilled.
6. Defective suction pressure
transducer/low pressure switch or
wiring.
7. Fans not operating (in heating mode).
1. Discharge service valve not open or
valve defective.
2. Condenser fans not operating or
operating backwards.
3. Too much refrigerant.
4. Air in refrigerant system.
5. Defective discharge pressure
transducer.
6. Compressor motor locked.
Email: sales@cookeindustries.co.nz
FORM NO.:6U6K-B01E-NB-EN
SOLUTION
1 a. Check wiring and power supply.
b. Check wiring emergency stop contacts
of terminal block.
c. Replace Control Transformer.
2. Check wiring Control Transformer to
Microboard.
3. Replace Control Transformer.
4. Replace
IPU3
& I/O Board or the
Display Board.
C o n ta ct Y O R K S ervice
b efore rep la cin g circu it
b o a rd s!
1. Check chilled liquid flow.
2. Purge the air though a release valve.
3. Check that the flow switch is installed
according to manufacturer's instructions.
4. Replace flow switch.
5. Check cycling devices connected to
terminals of the terminal Block.
1. Open or replace suction service
valve.
2. Repair leak if necessary and add
refrigerant.
3. Clean BPHE.
4. Check the wiring, or replace EEV.
5. Check liquid flow rate. Check operation of
pump, clean pump strainer, purge chilled
liquid system of air.
6. Replace transducer/low pressure switch or
faulty wiring.
7. Check fan wiring and communication.
1. Open or replace discharge service valve.
2. Check fan motor, and contactors. Assure
fan blows air upward.
3. Remove refrigerant.
4. Evacuate and recharge system.
5. Replace discharge pressure
transducer.
6. Replace compressor (and oil if
necessary).